Hrc Fuse Holder System With Spin-Rivetted Carrier Contact

Product Profile of Hrc Fuse Holder System With Spin-Rivetted Carrier Contact
HRC Fuse Holder System with Spin-Rivetted Carrier Contact is used for crimping type socket or soldering socket when connecting aluminum cable. Hitech Switchgear [India] offers HRC Fuse Holder System with Spin-Rivetted Carrier Contact. Hitech Switchgear [India] supplies various types of fuse links, fuse bases, fuse fittings & switch disconnetor fuse units for protection of electrical & electronic circuit & power distribution products. HRC Fuse Holder System with Spin-Rivetted Carrier Contact is attached with carrier contact which is spin-riveted and fitted in the molding to ensure perfect alignment with the base contacts.

HRC Fuse Holder System with Spin-Rivetted Carrier Contact has the following features:
  • Range : FFB, FFDM, FFPO 20, 32, 63 & 100A
  • Aperture giving visible indication of operation of HBC fuses links in mounted position.
  • Carrier contact spin-rivetted and fitted in the molding to ensure perfect alignment with the base contacts.
  • Brass base contact block with adequate cable hole to accommodate aluminum conductors.
  • Advisable to use crimping type socket or soldering socket when connecting aluminum cable.
  • Aluminum conductors can also be directly pinched in the terminal bore of the fuse fitting by adopting the following procedure:-
  • The individual stand of the cable should be spread-out and cleaned with wire wool or emery paper. The cleaned surface should be coated with a thin layer of suitable oxide inhibiting grease.
  • The cables may be terminated using the right size of screw driver for the grub screws and tightened fully.
  • Over tightening of use of bigger screws driver should be avoided.
  • At regular intervals tightness may be checked with the right screw driver.
  • Should the conductors be disturbed from the terminal bore, it is desirable to remake the connections
  • Product Specification of Hrc Fuse Holder System With Spin-Rivetted Carrier Contact
    • Rated Current: 2A to 100A
    • Rated Voltage: 415V A.C. 50 Hz
    • Breaking Capacity: 80 KA at 415 V A.C. 50 Hz
    • Type: FFB, FFDM, FFPO